ASHTABULA, OH —
OSHA Inspection: ZEHRCO-GIANCOLA COMPOSITES INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ZEHRCO-GIANCOLA COMPOSITES INC. in 1501 W.47ST., ASHTABULA, OH 44004 (NAICS 326199). OSHA activity number 344473970.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ZEHRCO-GIANCOLA COMPOSITES INC.
- Site address
- 1501 W.47ST.
- City
- ASHTABULA
- State
- OH
- ZIP
- 44004
- Mailing
- 5500 WASHINGTON AVE., ASHTABULA, OH 44004
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 55
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.107 B05 II
- Issued
- Mar 9, 2020
- Abate by
- Apr 2, 2020
- Penalty
- Initial $6,940 · Current $0 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(ii): Discarded filter pads and filter rolls were not immediately removed to a safe, well-detached location or placed in a water-filled metal container and disposed of at the close of the day's operation when not maintained completely in water: On or about November 14, 2019, the employer failed to ensure that filter pads used during two-part spray finishing operations at the facility were properly discarded. Used filters that contained residual/leftover material from a category 3 flammable /combustible chemical (Polylite 33282-07: Styrene/resin and fiber glass mixture) were thrown in a garbage can outside of the facility.
Recent events (2)
- — I (O) $0
- — Z (S) $6940
1910.303 B07 I
- Issued
- Mar 9, 2020
- Penalty
- Initial $5,205 · Current $3,470 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: On or about November 14, 2019, the employer failed to ensure that several of the company's junction boxes, located on the southwest wall next to the updraft paint booth were effectively closed. The 110/220/480 volts, 3 phase junction boxes were missing a knockout cover and thus had the potential to expose employees to electrical hazards from the wiring contained within the unit.
Recent events (2)
- — I (S) $3470
- — Z (S) $5205
1910.303 G02 I
- Issued
- Mar 9, 2020
- Penalty
- Initial $5,205 · Current $3,470 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph: On or about November 14, 2019, the 110/220/480 volts, 3 phase electrical junction box located on the southwest wall of the facility adjacent to the company's spray booth was missing the panel door. Employees tasked with completing a two part spray finishing application within the immediate vicinity of the spray booth were not protected from electrical hazards should over spray, dust or other material inadvertently contact the live parts of the electrical equipment.
Recent events (2)
- — I (S) $3470
- — Z (S) $5205
1910.305 G02 III
- Issued
- Mar 9, 2020
- Penalty
- Initial $5,205 · Current $3,470 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about November 14, 2019, adequate strain relief was not provided for the rigid conduit that fed into the 110/220/480 volts, 3 phase electrical panel, located on the southwest wall of the production area; adjacent to the updraft spray booth. The conduit fitting and/or connector used for routing the electrical wires into the panel box was not attached thus potentially exposing workers who frequent the area to electrical hazards should the wiring be damaged and/or ripped out.
Recent events (2)
- — I (S) $3470
- — Z (S) $5205
More inspections at Zehrco-Giancola Composites INC.
View Zehrco-Giancola Composites INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344473970.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.