Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACCEL, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACCEL, INC. in 9000 SMITH'S MILL ROAD, NEW ALBANY, OH 43054 (NAICS 561910). OSHA activity number 345241202.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Accel, INC. — free Get an email when a new federal OSHA severe-injury report for Accel, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
ACCEL, INC.
Site address
9000 SMITH'S MILL ROAD
City
NEW ALBANY
State
OH
ZIP
43054
Mailing
9000 SMITH'S MILL ROAD, NEW ALBANY, OH 43054
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561910
Employees
254
Ownership type
A

3 citations on file for this inspection.

1910.303 B07 I

Serious Gravity 5 1 instance 1 exposed
Issued
May 5, 2021
Penalty
Initial $10,728 · Current $5,000 Reduced
29 CFR  1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.  a) Accell, Inc. located at 9000 Smith's Mill Road, New Albany, Ohio 43054: On and preceding April 5, 2021, the employer did not ensure that unused openings in circuit breaker boxes were effectively closed. A piece of cardboard was used to cover a missing circuit breaker at location 38 of the circuit breaker panel P12, thereby exposing employees to a 110/220 volt electrical contact hazard.
Recent events (3)
  • — F (S) $5000
  • — C (S) $10728
  • — Z (S) $10728

1910.303 B07 IV

Serious Gravity 5 2 instances 1 exposed
Issued
May 5, 2021
Penalty
Initial $10,728 · Current $3,000 Reduced
29 CFR  1910.303(b)(7)(iv):There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.  a) Accell, Inc. located at 9000 Smith's Mill Road, New Albany, Ohio 43054: On and preceding April 5, 2021, the employer did not ensure that there were no damaged electrical parts. The lower front cover of electrical panel P10 was bent outwards, thereby exposing employees to a 110/220 volt electrical contact hazard.  b) Accell, Inc. located at 9000 Smith's Mill Road, New Albany, Ohio 43054: On and preceding April 5, 2021, the employer did not ensure that there were no damaged electrical parts. The lower front cover of electrical panel P9 was bent outwards, thereby exposing employees to a 110/220 volt electrical contact hazard.
Recent events (3)
  • — F (S) $3000
  • — C (S) $10728
  • — Z (S) $10728

1910.303 G01

Other-than-serious 2 instances 20 exposed
Issued
May 5, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1):Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.  a) Accell, Inc. located at 9000 Smith's Mill Road, New Albany, Ohio 43054: On and preceding April 5, 2021, the employer did not ensure that sufficient access and working space around circuit breaker panels was maintained. Product was stored within 36 inches of the P3 110/220 volt circuit breaker panel.  b) Accell, Inc. located at 9000 Smith's Mill Road, New Albany, Ohio 43054: On and preceding April 5, 2021, the employer did not ensure that sufficient access and working space around circuit breaker panels was maintained. Product was stored within 36 inches of the Line White 9B 110/220 volt circuit breaker panel.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

View Accel, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345241202.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.