ELLINGTON, CT —
OSHA Inspection: NATURAL COUNTRY FARMS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of NATURAL COUNTRY FARMS, INC. in 58 WEST ROAD, ELLINGTON, CT 06029 (NAICS 311411). OSHA activity number 345809644.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NATURAL COUNTRY FARMS, INC.
- Site address
- 58 WEST ROAD
- City
- ELLINGTON
- State
- CT
- ZIP
- 06029
- Mailing
- 58 WEST STREET, ELLINGTON, CT 06029
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311411
- Employees
- 82
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.303 E01 I
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $6,837 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(i): Electric equipment was used without the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified: Maintenance Shop: On, or about, April 1, 2022, a wall mounted panelboard that energized water heaters, outlets and another panel was not provided with the manufacturer's information or other markings to indicate the manufacturer. The panel board was provided with Square D circuit breakers. The door was missing, which may have contained the labels for the enclosure.
Recent events (2)
- — I (O) $2000
- — Z (S) $6837
1910.303 E01 II
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Markings were not provided on electrical equipment for voltage, current, wattage and other ratings as necessary: Maintenance Shop: On, or about, April 1, 2022, a wall mounted panelboard that energized water heaters, outlets and another panel was labeled with the voltage for the enclosure. Based on the use of single pole, double pole and three pole breakers, the enclosure appeared to be 120/208 volts. The door was missing, which may have contained the labels for the enclosure.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 F02
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Maintenance Shop: On, or about, April 1, 2022, the following branch circuits were not identified in the wall mounted panel board provided with Square D circuit breakers: 1, 2, 3-5-7, 4, 6-8-10, 9, 15, 18 and 20.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Apr 12, 2022
- Penalty
- Initial $5,811 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Maintenance Department: On, or about, April 1, 2022, access to the following electrical panels was blocked by items in storage: A. Square D 480/277 volt panel labeled "HV Maint. Shop". B. Square D 120/208 volt panel. No label.
Recent events (2)
- — I (O) $0
- — Z (S) $5811
1910.332 B01
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $11,396 · Current $8,000 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Plant: On, or about, April 1, 2022, Maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live electrical work, live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $8000
- — Z (S) $11396
1910.332 B02
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety: Plant: On, or about, April 1, 2022, an employee who did not meet the criteria of a "qualified person" performed tasks such as diagnostic testing and programming of machines and equipment while the equipment was live. The employee had not received training regarding electrical circuits and equipment, could not identify the voltage of the electrical enclosures that were accessed, was not familiar with the components inside of the enclosures and did not understand the potential hazards associated with the equipment. Abatement Note: Under Notes 1 and 2 of the definition of "Qualified person" in 29 CFR 1910.399, an unqualified person can perform certain tasks if provided with proper training, has demonstrated skills for the task(s) an is under the direction of a qualified person.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $14,502 · Current $10,000 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Plant: Personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, fire resistive balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized. In addition, non-fire resistive hair nets were worn by employees while working on or near live electrical equipment.
Recent events (2)
- — I (S) $10000
- — Z (S) $14502
1910.305 B01 I
- Issued
- Apr 12, 2022
- Abate by
- May 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: Production Floor, Pallet Highway: On, or about, April 1, 2022, conductors exiting the Wulftec control box were not secured in proper fittings, they appeared to be secured with electrical tape.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Natural Country Farms, INC.
View Natural Country Farms, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311411)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345809644.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.