OSHA Inspection: NAVAL SUPPLY SYSTEMS COMMAND - FLEET LOGISTICS CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVAL SUPPLY SYSTEMS COMMAND - FLEET LOGISTICS CENTER in 661 ROGERS ROAD, SAN DIEGO, CA 92118 (NAICS 928110). OSHA activity number 345941520.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval Supply Systems Command - Fleet Logistics Center — free Get an email when a new federal OSHA severe-injury report for Naval Supply Systems Command - Fleet Logistics Center is published. One employer, no account, unsubscribe in one click.
Site address
661 ROGERS ROAD
City
SAN DIEGO
State
CA
ZIP
92118
Mailing
661 ROGERS ROAD, SAN DIEGO, CA 92118
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
23
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 10, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Building 661:  On or before May 05, 2022, in the follow locations, appliances and other electrical equipment were plugged into power taps and/or extension cords and were not used according to listing and labeling instructions.  a) Shipping and Packing work area:  A Whirlpool refrigerator and a Walmart Microwave were plugged directly into a relocatable power tap. b) ASD Break area:  Avanti and Hamilton Beach microwaves were plugged into a relocatable power tap. c) ASD employee desk:  A Keurig coffeemaker was plugged directly into a relocatable power tap. d) TARP work area:  multiple pieces of electrical equipment such as StraPack Strapping Machine,  PACK Handheld Portable Heat Sealer, Sealed Air NewAir I.B. Express Instant Bubble Roll Machine were plugged into the same relocatable tap.  e) ATAC work area, employee desk:  A heater was plugged directly into a relocatable power tap.  Employees were exposed to electrical shock and/or fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 10, 2022
Abate by
Jul 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):  The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Building 661:  Packing and Shipping workcenter:  On or before May 05, 2022, the employer permitted materials to be directly stored in front of two different electrical panels located in Bay 2. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition exposed employees to an electrical and/or fire hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 10, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A):  Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Building 661, ASD workcenter:  On or before May 05, 2022, employee(s) used a portable extension cord as permanent power to power items such as a full size refrigerator. Employee(s) were exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

View Naval Supply Systems Command - Fleet Logistics Center's full OSHA safety record →