SAN DIEGO, CA —
OSHA Inspection: NAVAL SUPPLY SYSTEMS COMMAND - FLEET LOGISTICS CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NAVAL SUPPLY SYSTEMS COMMAND - FLEET LOGISTICS CENTER in ROGERS RD, BLDG. 661, SAN DIEGO, CA 92118 (NAICS 541614). OSHA activity number 347286825.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- ROGERS RD, BLDG. 661
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92118
- Mailing
- ROGERS RD, BLDG. 661, SAN DIEGO, CA 92135
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541614
- Employees
- 30
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.30 A02
- Issued
- Apr 2, 2024
- Abate by
- May 10, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.30(a)(2): The employer did not ensure that each employee is trained by a qualified person. Warehouse, Bldg. 661: On and/or before January 15, 2024, employees were not effectively trained by a qualified person on the fall protection procedures necessary to protect employees being exposed to fall hazards of 18 feet. This condition potentially exposed employee(s) to fall hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Apr 2, 2024
- Abate by
- Apr 8, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage. Transportation Office, Bldg. 661: On and/or before January 15, 2024, the employer did not ensure at least 3 feet in front of the electrical panel was clear. The circuit breaker panel had three(3) Sanitaire vacuum cleaner(s) obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Apr 2, 2024
- Abate by
- Apr 8, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. Warehouse, Conference Room, Bldg. 661: On and/or before January 15, 2024, flexible cords and/or cables were used as a source of permanent power for the computer tower that was placed on the floor behind the fire suppression system. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1960.8 A
- Issued
- Apr 2, 2024
- Abate by
- Apr 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm to employees from hazards associated with posting maximum safe load limits on pallet racks. Warehouse, Bldg. 661: On and/or before January 15, 2024, employee(s) used forklift(s) to load/unload heavy equipment. The industrial rack(s) did not have any postings of safe load limits. This condition potentially exposed employee(s) to Tip over/crushing hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 E03
- Issued
- Apr 2, 2024
- Abate by
- Apr 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check. On and/or before January 15, 2024, the fire extinguishers had not been subjected to their annual maintenance check(s). This condition potentially exposed employee(s) to fire hazards. In the following location(s): a) Bldg. 661, Bay 1 - 1E Aisle b) Bldg. 661, Bay 1 - 1G Aisle c) Bldg. 661, Bay 1 - 1R Aisle d) Bldg. 661, Bay 1 - Classified Bault e) Bldg. 661, Bay 1 - Outside Puk Office f) Bldg. 661, Bay 2 - Issuing Desk g) Bldg. 661, Bay 2 - 140 Location h) Bldg. 661, Bay 2 - 150 Location i) Bldg. 661, Bay 2 - 2L RFI Location j) Bldg. 661, Bay 2 - Forklift Recharge Area k) Bldg. 661, Bay 2 - Office Hallway l) Bldg. 661, Bay 2 - Eyewash/Shower Area m) Bldg. 661, Bay 2 - 5G Area n) Bldg. 661, Bay 3 - Receiving Area o) Bldg. 661, Bay 3 - Tarp Shack Naval Supply Systems Command was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.157(e)(3), which was contained in OSHA inspection number 1636224, citation number 2, item number 1 and was affirmed as a final order on January 13, 2022, with respect to a workplace located at 3985 Cummings Road, San Diego, CA 92136.
Recent events (2)
- — I (R) $0
- — Z (R) $0
More inspections at Naval Supply Systems Command - Fleet Logistics Center
View Naval Supply Systems Command - Fleet Logistics Center's full OSHA safety record →
More inspections in this industry (NAICS 541614)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347286825.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.