Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAVAL AIR WEAPONS STATION, CHINA LAKE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVAL AIR WEAPONS STATION, CHINA LAKE in HALL MEMORIAL LANES BLDG. 01092, RIDGECREST, CA 93555 (NAICS 713950). OSHA activity number 346299902.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval AIR Weapons Station, China Lake — free Get an email when a new federal OSHA severe-injury report for Naval AIR Weapons Station, China Lake is published. One employer, no account, unsubscribe in one click.
Site address
HALL MEMORIAL LANES BLDG. 01092
City
RIDGECREST
State
CA
ZIP
93555
Mailing
1 ADMINISTRATIVE CIRCLE, RIDGECREST, CA 93555
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713950
Employees
7
Ownership type
D

6 citations on file for this inspection.

1910.212 A

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 14, 2022
Abate by
Feb 2, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a): One or more methods of machine guarding were not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  Pin Setter Area: On and/or before October 18, 2022 employee(s) walked past the pin setter machines to service them during times of operation. The side(s) of the machines located at walkway isles were not guarded. This condition potentially exposed employee(s) to unguarded moving machine parts and/or amputation hazard(s).
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 14, 2022
Abate by
Jan 11, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Kitchen Backroom: On and or before October 18, 2022 the employer permitted chest freezers to be stored directly in front (within 36 inches) of the electrical panel(s). This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. Employee(s) were potentially exposed to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 14, 2022
Abate by
Dec 27, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords were being used as a permanent source for wiring:  Pin Setter Area: On and or before October 18, 2022 a flexible portable extension cord used to power an air compressor was used as a source of permanent power which had been in place since 2017.  This condition potentially can cause equipment failure. Employee(s) were subjected to potential electric shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 14, 2022
Abate by
Jan 11, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  Snack Bar: On and/or before October 18, 2022 Employee(s) used the TYURBOCHEF oven to cook pizzas for consumer consumption. The powercords exterior sheathing was pulled from the terminal joint (strain relief) exposing the inner insulated wires.  This condition potentially exposed employee(s) to electric shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 14, 2022
Abate by
Dec 27, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  Pin Setter Area: Employee(s) used the shop vacuum to clean. The Master Craft Vacuum (Shop VAC) had damage to the outer insulated jacket and the inner wires were spliced together.  This condition potentially exposed employee(s) to electric shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.101 A

Other-than-serious 1 instance 2 exposed
Issued
Dec 14, 2022
Abate by
Dec 27, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.101(a): The employer did not determine that compressed gas cylinders under his control were in a safe condition to the extent that can be determined by visual or other inspections conducted as prescribed in the Hazardous Materials Regulations.  Snack Bar: On and or Before October 18, 2022 the compressed cylinder used to carbonate liquid consumables was not properly secured to prevent it from being knocked over. This condition potentially exposed employee(s) to trip, an/or struck by hazards.
Recent events (1)
  • — Z (O) $0

View Naval AIR Weapons Station, China Lake's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346299902.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.