Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FLEX-N-GATE OKLAHOMA, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FLEX-N-GATE OKLAHOMA, LLC in 1 GENERAL STREET, ADA, OK 74820 (NAICS 326199). OSHA activity number 346761794.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Flex-N-Gate Oklahoma, LLC — free Get an email when a new federal OSHA severe-injury report for Flex-N-Gate Oklahoma, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1 GENERAL STREET
City
ADA
State
OK
ZIP
74820
Mailing
1 GENERAL STREET, ADA, OK 74820
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
200
Ownership type
A

5 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 1 2 instances 2 exposed
Issued
Nov 30, 2023
Abate by
Dec 27, 2023
Penalty
Initial $6,026 · Current $3,616 Reduced
29 CFR  1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910.  On or about June 8, 2023 and times prior thereto, 11A re-grinder area, two electrical panels were blocked with boxes and debris. This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $3615.6
  • — Z (S) $6026

1910.305 B01

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 30, 2023
Abate by
Dec 27, 2023
Penalty
Initial $6,026 · Current $3,616 Reduced
29 CFR  1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed:  On or about June 8, 2023 and at times prior thereto, Building 2, an opening was not effectively closed where conductors entered an electrical box of a re-grinder and the conduit was disconnected from the electrical box.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $3615.6
  • — Z (S) $6026

1910.305 G02 III

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 30, 2023
Abate by
Dec 27, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  On or about June 8, 2023 and at times prior thereto, at Building 2, strain relief was not provided to conductors that entered an electrical box of a re-grinder, where the conduit was disconnected.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 X

Other-than-serious 1 instance 2 exposed
Issued
Nov 30, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(a)(2)(x):  Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  On or about and times prior to June 8, 2023, 11A Re-grinder Area, an electrical extension cord supported on a sheet metal wall edge was not protected from accidental damage and exposed employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV

Other-than-serious 1 instance 2 exposed
Issued
Nov 30, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):   On or about June 8, 2023 and at times prior thereto, 11A Re-grinder Area, an extension cord ran through a sheet metal wall hole and exposed employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Flex-N-Gate Oklahoma, LLC's full OSHA safety record →