Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: V & V SUPREMO FOODS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of V & V SUPREMO FOODS, INC. in 2141 SOUTH THROOP STREET, CHICAGO, IL 60608 (NAICS 311513). OSHA activity number 347775660.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch V & V Supremo Foods, INC. — free Get an email when a new federal OSHA severe-injury report for V & V Supremo Foods, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2141 SOUTH THROOP STREET
City
CHICAGO
State
IL
ZIP
60608
Mailing
2141 S. THROOP ST., CHICAGO, IL 60608
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311513
Employees
60
Ownership type
A

2 citations on file for this inspection.

1910.37 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 13, 2024
Penalty
Initial $11,524 · Current $5,800 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a) Maintenance Shop - On or about September 24, 2024, the maintenance shop north exit door sign was not mounted. The employer failed to ensure the exit sign was clearly visible, thereby exposing employees to hazards associated with fire or other emergency evacuation hazards.
Recent events (2)
  • — I (S) $5800
  • — Z (S) $11524

1910.303 G01

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 13, 2024
Penalty
Initial $11,524 · Current $5,800 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a) Maintenance Shop - On or about September 24, 2024, the employer did not ensure a thirty-six (36) inch clearance pathway to electrical breaker panels. Employees were exposed to electrical hazards from the pathway being less than three (3) feet wide.
Recent events (2)
  • — I (S) $5800
  • — Z (S) $11524

View V & V Supremo Foods, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347775660.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.