DEDEDO, GU —
OSHA Inspection: XIANG WANG CONSTRUCTION CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of XIANG WANG CONSTRUCTION CORPORATION in LIN'S JEWELERY MICRONESIA MALL, SUITE 132, DEDEDO, GU 96929 (NAICS 238350). OSHA activity number 338908759.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- XIANG WANG CONSTRUCTION CORPORATION
- Site address
- LIN'S JEWELERY MICRONESIA MALL, SUITE 132
- City
- DEDEDO
- State
- GU
- ZIP
- 96929
- Mailing
- P.O. BOX 315752, TAMUNING, GU 96931
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238350
- Employees
- 10
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.102 A01
- Issued
- Mar 14, 2013
- Abate by
- Mar 20, 2013
- Penalty
- Initial $1,440 · Current $1,440
General-duty citation text
29 CFR 1926.102(a)(1): Eye and face protective equipment were not used when machines or operations presented potential eye or face injury from physical, chemical, or radiation agents. At the back wall of suite 132, on or about February 20, 2013, eye protection was not worn while using a Bosch 11255VSR BULLDOG Xtreme Rotary Hammer to drill holes in the concrete floor.
Recent events (1)
- — Z (S) $1440
1926.403 I02 I
- Issued
- Mar 14, 2013
- Abate by
- Mar 20, 2013
- Penalty
- Initial $2,520 · Current $2,520
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. At the back wall of suite 132, on or about February 20, 2013, the panel box was missing its dead front cover to prevent employees from accidental contact with live electrical parts.
Recent events (1)
- — Z (S) $2520
1926.404 B01 I
- Issued
- Mar 14, 2013
- Abate by
- Mar 20, 2013
- Penalty
- Initial $1,440 · Current $1,440
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. At the back wall of suite 132, on or about February 20, 2013, there was no assured equipment grounding conductor program or ground-fault circuit-interrupter program when an extension cord was used to supply power to a Bosch 11255VSR BULLDOG Xtreme Rotary Hammer. Employee used the drill to penetrate the concrete floor.
Recent events (1)
- — Z (S) $1440
1926.404 F06
- Issued
- Mar 14, 2013
- Abate by
- Mar 20, 2013
- Penalty
- Initial $1,440 · Current $1,440
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: At the back wall of suite 132, on or about February 20, 2013, the grounding pin was missing on the extension yellow extension cord that supplied power to a 110 VAC Bosch 11255VSR BULLDOG Xtreme Rotary Hammer. Employee used the drill to penetrate the concrete floor.
Recent events (1)
- — Z (S) $1440
1926.405 G02 IV
- Issued
- Mar 14, 2013
- Abate by
- Mar 20, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: At the project on or about February 20, 2013, a yellow 50 foot yellow extension cord's outer insulation was not secured to the plug. The cord supplied power to a 110 VAC 110 VAC Bosch 11255VSR BULLDOG Xtreme Rotary Hammer. Employee used the drill to penetrate the concrete floor.
Recent events (1)
- — Z (S) $0
More inspections at Xiang Wang Construction Corporation
View Xiang Wang Construction Corporation's full OSHA safety record →
More inspections in this industry (NAICS 238350)
More inspections in GU
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338908759.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.