AUSTIN, TX —
OSHA Inspection: DELSTAR TECHNOLOGIES, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of DELSTAR TECHNOLOGIES, INC. in 220 EAST SAINT ELMO ROAD, AUSTIN, TX 78745 (NAICS 326199). OSHA activity number 339691909.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DELSTAR TECHNOLOGIES, INC.
- Site address
- 220 EAST SAINT ELMO ROAD
- City
- AUSTIN
- State
- TX
- ZIP
- 78745
- Mailing
- 220 EAST SAINT ELMO ROAD, AUSTIN, TX 78745
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 157
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.95 C01
- Issued
- May 27, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $2,250 · Current $1,350 Reduced
General-duty citation text
29 CFR 1910.95(c)(1): The employer did not administer a continuing, effective hearing conservation program as described in 29 CFR 1910.9(c) through (o) whenever employee noise exposures equal or exceed an 8-hour time-weighted average sound level of 85 decibels measured on the A scale, or equivalently a dose of fifty percent: On or about April 18, 2014, the employer did not institute an effective hearing conservation program for employees exposed to noise levels in excess of the allowable 8-hour Time Weighted Average (TWA) action level of 85 dBA. a: Dosimetry performed on a production employee for 459 minutes indicated that the employee was exposed to a 72.99% noise dose which is equivalent to approximately 87.73 dBA. b: Dosimetry performed on a machine operator for 477 minutes indicated that the employee was exposed to a 85.36% dose which is equivalent to approximately 88.86 dBA. Elements of a hearing conservation program include, but are not limited to, sound level monitoring, audiometric testing on all affected employees, hearing protection, training, and record keeping.
Recent events (2)
- — I (S) $1350
- — Z (S) $2250
1910.305 G01 IV A
- Issued
- May 27, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $3,000 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure On or about April 18, 2014, flexible cords were used as permanent wiring, exposing employees an electrical hazard. a: An extension cord was used as permanent wiring and affixed to the structure to power a 110 volt fan near the slitter. The cord was run from an outlet, up a beam, and down to where the fan was used. b: An extension cord in the munchy room was used as permanent wiring and affixed to the structure to power a 220 volt sump pump. The cord was ran from an outlet and along a wall to the sump pump.
Recent events (2)
- — I (S) $1800
- — Z (S) $3000
1910.305 G01 IV D
- Issued
- May 27, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: On or about April 18, 2014, flexible cords were affixed to the structure and used as permanent wiring, exposing employees an electrical hazard. a: An extension cord was used as permanent wiring and affixed to the structure to power a 110 volt fan near the slitter. The cord was run from an outlet, up a beam, and down to where the fan was used. b: An extension cord in the munchy room was used as permanent wiring and affixed to the structure to power a 220 volt sump pump. The cord was ran from an outlet and along a wall to the sump pump.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J02 I
- Issued
- May 27, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(i): No receptacles may be installed so as to require an energized attachment plug as its source of supply: On or about April 18, 2014, a flexible cable was cut and used to power a receptacle box which, in turn, powered a water cooler and UV bug light, exposing employees to an electrical hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Delstar Technologies, INC.
View Delstar Technologies, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339691909.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.