Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DELSTAR TECHNOLOGIES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DELSTAR TECHNOLOGIES, INC. in 601 INDUSTRIAL ROAD, MIDDLETOWN, DE 19709 (NAICS 326113). OSHA activity number 345769038.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Delstar Technologies, INC. — free Get an email when a new federal OSHA severe-injury report for Delstar Technologies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
601 INDUSTRIAL ROAD
City
MIDDLETOWN
State
DE
ZIP
19709
Mailing
601 INDUSTRIAL DRIVE, MIDDLETOWN, DE 19709
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326113
Employees
230
Ownership type
A

10 citations on file for this inspection.

1910.147 C04 II

Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $14,502 · Current $11,601 Reduced
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D):    a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (Throughout facility ): On or about February 14,2022, and various days prior the employer failed to ensure that the developed energy control procedures clearly identified specific steps to be followed to control hazardous energy for various equipment throughout site such as but not limited to DELNET LINE 1 on which employees perform set up, servicing, installing and cleaning.    NOTE: The procedures must be documented in sufficient detail and provide enough direction so that employees can effectively follow the procedure and determine how to safely perform the servicing and maintenance activities. Over generalization can result in a document which has little or no utility to the employee who must follow procedure. However, while the procedure is required to be written in detail, this does not mean that a separate procedure must be written for each and every machine or piece of equipment. Similar machines and/or equipment (those using the same type and magnitude energy) that has the same or similar types of controls can be covered with a single procedure.
Recent events (3)
  • — F (S) $11601.4
  • — C (S) $14502
  • — Z (S) $14502

1910.147 C07 I B

Deleted Serious Gravity 5 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(7)(i)(B): Affected employees were not instructed in the purpose and use of the energy control procedure:   a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1 ): On or about February 14,2022, operators who routinely operate DELNET Line 1  machines were not provided training in the recognition of applicable hazardous energy sources, the type and magnitude of energy available in the workplace and the methods & means necessary for energy isolation.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 C05 II

Other-than-serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Penalty
Initial $14,502 · Current $7,000 Reduced
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were used for purposes other than for controlling energy during servicing and maintenance tasks:   a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1): On or about February 14,2022, Lockout tags were used for purposes other than controlling energy during servicing and maintenance at the Casting Stand disconnect box on DelNet Line 1.
Recent events (3)
  • — F (O) $7000
  • — C (S) $14502
  • — Z (S) $14502

1910.147 C06 I

Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (Throughout facility ): On or about February 14,2022, the employer failed to ensure a review of the developed written energy control procedure document DELNET LINE 1 - D1 was inspected annually on or about February 14, 2022.   b) 601 Industrial Road, Middletown, DE 19709: On or about February 14, 2022, the employer failed to ensure a review of the lockout/ tagout procedure document DELNET LINE 1 - D1 was inspected annually on or about February 14, 2022.    Abatement Note:    1. Where lockout should be used for energy control, the periodic inspection shall include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected.1910.147(c)(6)(i)(D)    2. Where tagout should be used for energy control, the periodic inspection shall include a review, between the inspector and each authorized and affected employee, of that employee's responsibilities under the energy control procedure being inspected, and the elements set forth in paragraph (c)(7)(ii) of this section.1910.147(c)(6)(ii)    3. The employer shall certify that the periodic inspections have been performed. The certification shall identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection.
Recent events (3)
  • — F (S) $0
  • — C (S) $14502
  • — Z (S) $14502

1910.147 C06 II

Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(ii):The employer did not certify that periodic inspections of the energy control procedures had been performed:(a)   a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (Throughout facility ): On or about February 14,2022, and various days prior, the employer failed to conduct periodic inspections and certify them to ensure that the developed energy control procedures clearly identified specific steps to be followed to control hazardous energy for equipment located on Delnet Line 1 - D1 on which employees performed servicing and cleaning.  Abatement Note:    1. Where lockout should be used for energy control, the periodic inspection shall include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected.1910.147(c)(6)(i)(D)    2. Where tagout should be used for energy control, the periodic inspection shall include a review, between the inspector and each authorized and affected employee, of that employee's responsibilities under the energy control procedure being inspected, and the elements set forth in paragraph (c)(7)(ii) of this section.1910.147(c)(6)(ii)    3. The employer shall certify that the periodic inspections have been performed. The certification shall identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.212 A01

Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $14,502 · Current $20,554
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1 ): On or about February 14,2022, and other various days before, The employer failed to provide the required level of guarding to protect its employees from ingoing nip points and other rotating parts while conducting normal operations at the ER/CR Pumps, the ER/CR roll Drive Gears, and the Tenter Exit on Line 1.
Recent events (3)
  • — F (S) $20554
  • — C (S) $14502
  • — Z (S) $14502

1910.212 A03 II

Deleted Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1 ): On or about February 14,2022, and other various days before, the employer failed to guard the ingoing nip points of extruder line #1, pre-stretch stand used to stretch material being processed through the line, exposing employees to caught in/amputation hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.216 C01

Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR  1910.216(c)(1):Safety tripod, cable, or wire center cord shall be provided across each pair of in-running rolls extending the length of the face of the rolls.  It shall be readily accessible and operate whether pushed  or pulled.  The safety tripping devices shall be located within reach of the operator and the bite.  a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1 Pre-stretch stand): On or about February 14,2022,and other various days before, the employer failed to guard the ingoing nip points of pre-stretch stand,  with a Safety tripod, cable, or wire center cord to protect workers for in-running rolls, exposing employees to caught in/amputation hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $14502
  • — Z (S) $14502

1910.303 B07

Deleted Serious Gravity 10 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner:  a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1 ): On or about February 14,2022, and other various days before, the employer failed to install or maintain electrical equipment in a neat and workmanship matter on DELNET Line #1.
Recent events (3)
  • — F (S) $0
  • — C (S) $14502
  • — Z (S) $14502

1910.305 A02 XI

Deleted Serious Gravity 5 1 instance 19 exposed
Issued
Aug 12, 2022
Abate by
Sep 8, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(xi): Cable assemblies and flexible cords and cables were not supported in place at intervals that ensure that they will be protected from physical damage:   a) Schweitzer-Mauduit International Inc., 601 Industrial Road, Middletown, DE 19709 (DELNET LINE 1): On or about February 14,2022, and other various days before, employees were exposed to flexible cords and cables which were unsupported and unprotected during operations.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Delstar Technologies, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345769038.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.