SCHOFIELD, WI —
OSHA Inspection: CRYSTAL FINISHING SYSTEMS, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CRYSTAL FINISHING SYSTEMS, INC. in 650 ALDERSON STREET, SCHOFIELD, WI 54476 (NAICS 332812). OSHA activity number 341024529.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CRYSTAL FINISHING SYSTEMS, INC.
- Site address
- 650 ALDERSON STREET
- City
- SCHOFIELD
- State
- WI
- ZIP
- 54476
- Mailing
- 2610 ROSS AVENUE, SCHOFIELD, WI 54476
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332812
- Employees
- 800
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.124 J01
- Issued
- Feb 5, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $3,740 · Current $2,618 Reduced
General-duty citation text
29 CFR 1910.124(j)(1): The employer did not inspect the hoods and ductwork of the dipping or coating operation ventilation system for corrosion or damage at least quarterly during operations and/or prior to operation after a prolonged shutdown: a) The employer had not developed a procedure to inspect the Anodizing Line ventilation system on a quarterly basis or prior to operation after a prolong shutdown.
Recent events (2)
- — I (S) $2618
- — Z (S) $3740
1910.124 J02
- Issued
- Feb 5, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.124(j)(2): The employer did not ensure the airflow of the dipping or coating operation ventilation system was adequate at least quarterly during operations and/or prior to operation after a prolonged shutdown: a) The employer had not developed a procedure to ensure the Anodizing Line ventilation airflow was adequate.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.124 J03
- Issued
- Feb 5, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.124(j)(3): Periodic inspections of all dipping and coating equipment, including covers, drains, overflow piping, and electrical and fire-extinguishing systems were not conducted, and deficiencies were not promptly corrected: a) The employer had not developed a procedure to ensure all components of the Anodizing Line were periodically inspected. b) On or about November 4, 2015, a 6 inch seam crack was observed on the Etching Tank #4 ventilation hood. c) Anodizing dip tank outer shell repairs were not consistent with recognized and generally accepted engineering practices.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Crystal Finishing Systems, INC.
View Crystal Finishing Systems, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332812)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341024529.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.