Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, ISLE ROYALE NATIONAL PARK

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, ISLE ROYALE NATIONAL PARK in MOTT ISLAND 800 EAST LAKESHORE DRIVE, HOUGHTON, MI 49931 (NAICS 712190). OSHA activity number 342880531.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Interior, National Park Service, Isle Royale National Park — free Get an email when a new federal OSHA severe-injury report for Department of Interior, National Park Service, Isle Royale National Park is published. One employer, no account, unsubscribe in one click.
Site address
MOTT ISLAND 800 EAST LAKESHORE DRIVE
City
HOUGHTON
State
MI
ZIP
49931
Mailing
800 EAST LAKESHORE DRIVE, HOUGHTON, MI 49931
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
75
Ownership type
D

15 citations on file for this inspection.

1910.137 C02 VIII

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.137(c)(2)(viii) as required  by 1960.8(b): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5.    On or about September 4, 2017,  on Mott Island, employee was required to disconnect power to the main 480v transformer due to a connect failure on the load side of the transformer and the employer did not provide rubber insulating gloves that were periodically tested within the last six months there by exposing employee to electrical shock hazard. The rubber insulating gloves were last tested September 01, 2011.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.180 D04

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.180(d)(4) as required by 1960.8(b): Complete inspection(s) of crane(s) were not performed at intervals as generally defined in 1910.180(d)(ii) with a determination made as to whether deficiencies constituted a safety hazard:    On or about September 13, 2017 on Mott Island, the employer did not ensure that at least monthly inspections were being conducted on the Lorain truck boom crane, model LRT-100 S/N: 97191 thereby exposing employees to struck by hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.184 C14

Serious Gravity 1 1 instance 3 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.184(f)(1) as required by 19060.8(b): Wire-rope slings did not  have permanently affixed and legible identification markings as prescribed by the manufacturer  that indicated the recommended safe working load for the type(s) of hitch(es) used, the angle upon which it is based, and the number of legs if more than one:      On or about September 13, 2017, on Mott Island, employees were exposed to being struck-by a fiberglass lift station that was being lifted with the Lorain truck boom crane, model LRT-100 S/N: 97191.  One 4-leg bridle wire rope sling and associated hooks and shackles were not marked with the safe working load.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.215 A02

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(2) as required by 1906.8(b): Abrasive wheel(s) used on grinding machinery were not provided with safety guard(s) which covered the spindle end, nut, flange projections:    On or about September 12, 2017, on Mott Island, Admin/shop building, the employer did not ensure that spindle and nut located on the right side of an abrasive wheel grinder was guarded there by exposing employees to a caught in hazard. The abrasive wheel grinder was used to brush a binder bolt used in a transformer repair.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 A02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 27, 2018
Abate by
Jul 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(i) as required by 1960.8(b):  All employees performing work covered by this section shall be trained as follows:     a.  Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.   b.  Each employee shall also be trained in and familiar with any other safety practices, including applicable emergency procedures (such as pole-top and manhole rescue), that are not specifically addressed by this section but that are related to his or her work and are necessary for his or her safety.           On or about September 4, 2017,  on Mott Island, the employer did not provide safety related work practices and pole top emergency procedures training to employee required to perform work on transformer pole located near the Mott Island Water tower there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 A02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
Jul 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(ii)as required by 1960.8(b): Each qualified employee shall also be trained and competent in:     a. The skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment.   b. The skills and techniques necessary to determine the nominal voltage of exposed live parts.   c. The minimum approach distance specified in this section corresponding to the voltages to which the qualified employee will be exposed, and   d. The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment:     On or about September 13, 2017, on Mott Island, the employer did not provide training to the employee who was designated to operate, maintain, and repair electrical equipment at the power generation station there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D02 III

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 27, 2018
Abate by
Jul 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(2)(iii) as required by 1960.8(b):  Procedures shall be developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section.    a. On or about September 04, 2017, on the Mott Island, the employer did not develop specific Lockout/tag out procedures for employees that were required to perform repair work on a step down transformers located on pole near the Mott Island Water treatment facility there by exposing employee to electrical shock hazard.      b. On or about September 13, 2017, in the Mott Island Power Generation Station, the employer did not develop specific Lockout/tag out procedures for performing maintenance and or repair of mechanical and electrical equipment specifically used for power transmission and distribution there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 K02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(k)(2)(i) as required by 1960.8(b):: In areas to which access is not restricted to qualified persons only, materials or equipment may not be stored closer to energized lines or exposed energized parts of equipment than the following distances:  a. For lines and equipment energized at 50 kilovolts or less, the distance is 3.05 meters (10 feet).    On or about September 13, 2017, on Mott Island, the employer did not ensure that a metal desk and metal podium used by employees is closer than ten feet from energized equipment such as but not limited to: 208v transformer there by exposing employees to electrical shock and arc flash hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 V04 III

Serious Gravity 5 1 instance 40 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(v)(4)(iii): Unqualified persons may not enter the rooms or other spaces while the electric supply lines or equipment are energized.    On or about September 13, 2017, on Mott Island, the employer did not ensure that unqualified persons do not access the power generation station there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 L03 III

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(3)(iii) as required by 1960.8(b): The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:  a. The employee is insulated from the energized part, or  b. The energized part is insulated from the employee and from any other conductive object at a different potential, or.   c. The employee is insulated from any other exposed conductive object in accordance with the requirements for live-line bare hand work in paragraph (q)(3) of this section.    On or about September 13, 2017, on Mott Island, in the power generation station, the employer did not establish minimum approach distances and did not ensure that conductive objects such as but not limited to: metal desk were kept safe distance from an energized 208v transformer there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 M03 VII

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
Jul 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.269(m)(3)(vii)as required by 1960.8(b): The employer did not ensure the installation of protective grounds as required by paragraph (n) of this section:     On or about September 04, 2017, on the Mott Island, the employer did not ensure that a protective ground was installed on the energized lines while an employee performed repair work on a step down transformer located on platform near the Mott Island Water treatment facility there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
Apr 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i) as required by 1960.8(b): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means:  a. By location in a room, vault, or similar enclosure that is accessible only to qualified persons;  b. Substantial partitions or screens so arranged so that only qualified persons would have access to the space within reach of the live parts;   c. By placement on a suitable balcony, gallery, or platform so elevated and otherwise located as to prevent access by unqualified persons; or  d. By elevation of 2.44 m (8.0 ft) or more above the floor or other working surface.    On or about September 13, 2017, on Mott Island, in the power generation station, the employer did not guard live parts of a 208v transformer designed to provide power to the generation there by exposing employees to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1) as required by 1960.8(b): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    On or about September 13, 2017, on Mott Island, the employer did not provide safety related work practices training to the employee who was designated to operate, maintain, and repair electrical equipment at the power generation station there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(2) as required by 1960.8(b): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety:    On or about September 13, 2017, on Mott Island, the employer did not provide electrical related work practices training to the employee who was designated but not a qualified person to operate, maintain, and repair electrical equipment at the power generation station there by exposing employee to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 M01

Other-than-serious 1 instance 2 exposed
Issued
Feb 27, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.179(m)(1) as required by 1960.8(b): Thorough monthly inspections of rope conditions, with written, dated and signed reports, were not performed on the running ropes:      On or about September 1, 2017, on Mott Island, the employer did not conduct monthly running rope inspections with a written certification record for the 9 ton Marine Travel-Lift, Model #9 AM, S/N 1288573. The travel lift was used to remove a boat from the water for maintenance.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Department of Interior, National Park Service, Isle Royale National Park's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342880531.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.