OREGON, OH —
OSHA Inspection: TOLEDO REFINING COMPANY LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TOLEDO REFINING COMPANY LLC in 1819 WOODVILLE RD., OREGON, OH 43616 (NAICS 324110). OSHA activity number 343078952.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TOLEDO REFINING COMPANY LLC
- Site address
- 1819 WOODVILLE RD.
- City
- OREGON
- State
- OH
- ZIP
- 43616
- Mailing
- 1819 WOODVILLE RD., OREGON, OH 43616
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 500
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 J06 III
- Issued
- Sep 26, 2018
- Abate by
- Oct 22, 2018
- Penalty
- Initial $12,934 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(6)(iii): The employer did not assure that maintenance materials, spare parts and equipment are suitable for the process application for which they were used: a) Toledo Refining Company, LLC - Oregon, Ohio: On or about April 11, 2018, the employer did not ensure that replacement components for the burner assembly in the H-9502 were suitable for the original design of the burner. The rebuild of the heater/burner following the March 1, 2018 incident included components from a different revision of the design of the equipment. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
- — F (S) $0
- — C (S) $12934
- — Z (S) $12934
1910.119 D03 II
- Issued
- Sep 26, 2018
- Abate by
- Feb 1, 2019
- Penalty
- Initial $12,934 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: a) Toledo Refining Company, LLC Oregon, Ohio: On or about April 11, 2018, the employer did not document that it had in place quality assurance steps, consistent with API Recommended Practice 535, Burners for Fire Heaters in General Refinery Services, sufficient to ensure that certain third-party supplied replacement components for a heater burner assembly were consistent with the then-current burner design.
Recent events (3)
- — F (O) $0
- — C (S) $12934
- — Z (S) $12934
More inspections at Toledo Refining Company LLC
View Toledo Refining Company LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343078952.