OREGON, OH —
OSHA Inspection: TOLEDO REFINING COMPANY LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of TOLEDO REFINING COMPANY LLC in 1819 WOODVILLE RD., OREGON, OH 43616 (NAICS 324110). OSHA activity number 343759130.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TOLEDO REFINING COMPANY LLC
- Site address
- 1819 WOODVILLE RD.
- City
- OREGON
- State
- OH
- ZIP
- 43616
- Mailing
- 1819 WOODVILLE RD., OREGON, OH 43616
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 500
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Jul 19, 2019
- Abate by
- Aug 13, 2019
- Penalty
- Initial $13,260 · Current $0 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that fire protection equipment was not maintained to protect against fire hazards: Toledo Refining Company, LLC - Oregon, Ohio: On or about February 3, 2019, the employer did not ensure fire protection equipment was maintained to protect employees in Tank Farm #2 from thermal hazards involved with an explosion/fire event. Multiple fire hydrants and monitors, including #20, 41, 42 and 62 were out of service, which hindered the emergency response personnel from extinguishing the fire. Among other methods, one feasible and acceptable method to correct this hazard includes, but is not limited to the following: Ensure that fire protection system equipment is inspected and maintained for its intended use of fire-fighting. NFPA 25 - Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems (2017), Section 4.1.5 states, "The property owner or designated representative shall correct or repair deficiencies or impairments."; and Section 7.4.1 states, "All equipment shall be maintained in proper working condition, consistent with the manufacturer's recommendations."
Recent events (3)
- — F (S) $0
- — C (S) $13260
- — Z (S) $13260
More inspections at Toledo Refining Company LLC
View Toledo Refining Company LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343759130.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.