OSHA Inspection: NOAH'S ARK PROCESSORS, LLC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of NOAH'S ARK PROCESSORS, LLC in 1009 W M ST, HASTINGS, NE 68901 (NAICS 424470). OSHA activity number 343461604.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Noah'S ARK Processors, LLC — free Get an email when a new federal OSHA severe-injury report for Noah'S ARK Processors, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1009 W M ST
City
HASTINGS
State
NE
ZIP
68901
Mailing
1009 W M ST, HASTINGS, NE 68901
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424470
Employees
480
Ownership type
A

16 citations on file for this inspection.

1910.28 B03 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Aug 22, 2019
Penalty
Initial $9,239 · Current $5,543 Reduced
29 CFR 1910.28(b)(3)(i): The employer must ensure each employee is protected from falling through any hole (including skylights) that is 4 feet (1.2 m) or more above a lower level:     The employer is failing to protect employees from fall hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. Where the employer has unprotected employees working on the roof of the structure exposed to fall hazards from the three inadequately protected skylights.
Recent events (3)
  • — F (S) $5543.4
  • — C (S) $9239
  • — Z (S) $9239

1910.119 D03 I E

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Dec 25, 2019
Penalty
Initial $12,934 · Current $10,000 Reduced
29 CFR 1910.119(d)(3)(i)(E): The employer did not have a compilation for written process safety information pertaining to the ventilation system design:      The employer is failing to protect employees from chemical hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The employer is failing to provide Process Safety Information for the ventilation system in engine room or the design basis for the ventilation. The engine room has no documented calculations that show the installed ventilation system in the engine room is sufficient for the engine room.
Recent events (3)
  • — R (S) $10000
  • — C (S) $12934
  • — Z (S) $12934

1910.119 E03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Dec 25, 2019
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process:      The employer is failing to protect employees from chemical hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The 2016 Process Hazard Analysis was performed, however, it failed to list or address any potential consequences of ammonia being vented back into the plant.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.307 C02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Dec 25, 2019
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:      The employer is failing to ensure that the workplace was free from explosion hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The electrical installations throughout the engine room are not designed for Class 1, Division 2 locations where flammable gases may be present in the area.  This room contains refrigeration equipment utilizing anhydrous ammonia which is a flammable gas.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.119 D03 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Dec 25, 2019
Penalty
Initial $9,239 · Current $5,543 Reduced
29 CFR 1910.119(d)(3)(ii):  The employer did not document that equipment complies with recognized and generally accepted good engineering practices:        a)  On or about July 24, 2018 at 1009 W M St., Hastings, Nebraska 68901, at the Noah's Ark Processors, LLC facility, the employer did not document that it complied with recognized and generally accepted good engineering practice (RAGAGEP), such as ANSI/IIAR 2-2014; ANSI/ASH RAE Standard lS-2013; and IIAR Bulletin 109, Section 4.7.6, when it did not ensure that ammonia refrigeration piping was labeled.       b)  On or about July 24, 2018 at 1009 W M St., Hastings, Nebraska 68901, at the Noah's Ark Processors, LLC facility, the employer did not document that it complied with recognized and generally accepted good engineering practice (RAGAGEP), such as ANSI/IIAR 2-2014; ANSI/ASH RAE Standard lS-2013; and IIAR Bulletin 109, Section 4.10.3, when it did not ensure the main shut off valve (King Valve) was clearly labeled.
Recent events (3)
  • — F (S) $5543.4
  • — C (S) $9239
  • — Z (S) $9239

1910.119 E03 V

Serious Gravity 10 1 instance 4 exposed
Issued
Jan 18, 2019
Abate by
Jul 8, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.119(e)(3)(v): Facility siting was not addressed to ensure process safety equipment was protected from impact:      The employer is failing to protect employees from chemical hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The employer failing to ensure that an ammonia vessel was protected from vehicular impact. The ammonia receiver is in a pathway toward the maintenance shop and the company has failed to install any  barriers to protect the receiver from being struck by vehicular impact.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.119 F04

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Aug 27, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.119(f)(4): The employer did not develop or implement safe work practices for employees and contractors performing maintenance activities on covered processes:      The employer is failing to protect employees from chemical burn hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The company has standard operating procedures written for operations for the ammonia refrigeration system; however, they fail to include procedures for de-energizing or making safe the system components prior to any activity were the ammonia could be released.  The operating procedures fail to outline procedures for locking out the covered equipment.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.119 J02

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Aug 27, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.119(j)(2): The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment:      The employer is failing to protect employees from chemical burn hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The company has a mechanical integrity program with some standard operating procedures for changing out process equipment; however, they have not developed procedures for multiple pieces of process equipment such as; but not limited to, Compressor #2 and the Unit in AC #1.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.119 J05

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Dec 25, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.119(j)(5): Equipment deficiencies. The employer shall correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation:      The employer is failing to protect employees from chemical hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The employer is failing to provide Process Safety Information for the safety system in the engine room, specifically no audio or visual alarms are in or outside of the engine room. The engine room is not equipped with alarms that audibly or visually indicate that an ammonia leak is present. Its chosen recognized and generally accepted good engineering practice (RAGAGEP), ANSI/IIAR 2-2014 ANSI/IIAR 2 -2014 (Standard for Safe Design of Closed-Circuit Ammonia Refrigeration Systems), Section 6.13.1 states that for ammonia detection for machinery rooms, audible and visual alarms shall be provided inside the room to warn that access to the room is restricted to authorized personnel and emergency responders when the alarm has activated. Additional audible and visual alarms shall be located outside of each entrance to the machinery room.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.119 N

Serious Gravity 10 1 instance 3 exposed
Issued
Jan 18, 2019
Abate by
Jul 8, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.119(n): The emergency action plan did not include procedures for handling small releases:      The employer is failing to protect employees from chemical burn hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. In the company written emergency action program there is no information for how employees are to differentiate between small releases and large releases and how to respond.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.147 C04 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 18, 2019
Abate by
Jul 28, 2019
Penalty
Initial $9,239 · Current $5,543 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:      The employer is failing ensure that employees are protected from the hazards of amputations and electrocutions. This most recently occurred at near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. There was no documentation provided by the employer that showed specific procedures for locking out equipment, including but not limited to the Four Quarter Saw on the Chuck Line and the Brisket Saw.
Recent events (3)
  • — F (S) $5543.4
  • — C (S) $9239
  • — Z (S) $9239

1910.151 C

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Jul 8, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:      a) On or about July 24, 2018 at 1009 W M St., Hastings, Nebraska 68901 the employer failed to ensure that an eyewash station was available for use outside of the engine room near the ammonia receiver and process equipment.    b) On or about July 24, 2018 at 1009 W M St., Hastings, Nebraska 68901 the employer failed to ensure in the engine room the eyewash shower was accessible due to a cabinet that was used to store extra parts obstructing the eyewash shower.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.157 G01

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Jul 8, 2019
Penalty
Initial $9,239 · Current $5,543 Reduced
29 CFR 1910.157(g)(1): Where the employer has provided portable fire extinguishers for employee use in the workplace, the employer did not provide an educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:      The employer is failing to protect employees from fire hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. In the company written emergency action program there is information for designated employees to be trained to fight incipient stage fires. There is no educational program in place for these employees.
Recent events (3)
  • — F (S) $5543.4
  • — C (S) $9239
  • — Z (S) $9239

1910.305 B02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Aug 22, 2019
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    The employer is failing to ensure that the workplace was free from electrical hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. In the engine room, there were electrical boxes on Compressors 1, 2, and 3 that had missing covers, exposing electrical wires.
Recent events (3)
  • — F (S) $7760.4
  • — C (S) $12934
  • — Z (S) $12934

1910.305 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 18, 2019
Abate by
Aug 27, 2019
Penalty
Initial $9,239 · Current $5,543 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:      The employer is failing to ensure that the workplace was free from electrical hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on October 17, 2018. There was an outlet box in the damp processing room that had a broken cover exposing electrical conductors.
Recent events (3)
  • — F (S) $5543.4
  • — C (S) $9239
  • — Z (S) $9239

1910.1200 H

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Mar 5, 2019
Penalty
Initial $7,391 · Current $0 Reduced
29 CFR 1910.1200(h): Employees were not provided effective information and training as specified in 29 CFR 1910.1200(h)(1) and -2 on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard was introduced into their work area:     The employer is failing to protect employees from chemical burn hazards. This violation was most recently documented at a worksite located at or near 1009 W M St., Hastings, Nebraska 68901 on July 24, 2018. The employer did not ensure that employees were provided with effective information and training in their work area at the time of their initial assignment with the hazards of ammonia.
Recent events (3)
  • — F (S) $0
  • — C (S) $7391
  • — Z (S) $7391