OSHA Inspection: MIDWEST ELASTOMERS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of MIDWEST ELASTOMERS, INC. in 700 INDUSTRIAL DR., WAPAKONETA, OH 45895 (NAICS 325212). OSHA activity number 343992897.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Midwest Elastomers, INC. — free Get an email when a new federal OSHA severe-injury report for Midwest Elastomers, INC. is published. One employer, no account, unsubscribe in one click.
Site address
700 INDUSTRIAL DR.
City
WAPAKONETA
State
OH
ZIP
45895
Mailing
700 INDUSTRIAL DR., WAPAKONETA, OH 45895
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325212
Employees
72
Ownership type
A

5 citations on file for this inspection.

1910.28 B07

Serious Gravity 5 4 instances 12 exposed
Issued
Aug 16, 2019
Abate by
Sep 4, 2019
Penalty
Initial $5,834 · Current $2,917 Reduced
29 CFR 1910.28(b)(7): The employer did not ensure that each employee on a walking-working surface near an opening 4 feet (1.2 m) or more above a lower level is protected from falling:    a. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 8, 2019, the employer did not ensure that the ladderway floor opening, located on the first elevated platform at the 02-Cryo line, was guarded to protect employees from fall hazards of approximately seven feet.   b.Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 8, 2019, the employer did not ensure that the ladderway floor opening, located on the second elevated platform at the 02-Cryo line, was guarded to protect employees from fall hazards of approximately four feet.  c. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 8, 2019, the employer did not ensure that the ladderway floor opening, located on the third (top) elevated platform at the 02-Cryo line, was guarded to protect employees from fall hazards of approximately eight feet.  d. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 8, 2019, the employer did not ensure that the ladderway floor opening, located at the 02-Cryo mill platform, was guarded to protect employees from fall hazards of approximately seven feet.
Recent events (2)
  • — I (S) $2917
  • — Z (S) $5834

1910.147 C06 I

Serious Gravity 10 1 instance 40 exposed
Issued
Aug 16, 2019
Abate by
Aug 27, 2019
Penalty
Initial $10,210 · Current $10,210
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  a. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 1, 2019, a periodic inspection of the energy control procedures was not performed to assure that lockout/tagout procedure and requirements of 29 CFR 1910.147 were being followed.  The employer did not assure that the energy control procedure for 02-Cryo line was inspected.
Recent events (2)
  • — I (S) $10210
  • — Z (S) $10210

1910.147 C07 III A

Serious Gravity 10 1 instance 40 exposed
Issued
Aug 16, 2019
Abate by
Oct 15, 2019
Penalty
Initial $10,210 · Current $0 Reduced
29 CFR 1910.147(c)(7)(iii)(A): Retraining was not provided for authorized and affected employees when there was a change in their job assignments, a change in machines, equipment or processes that presented a new hazard, or when there was a change in the energy control procedures.  a. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 1, 2019, the employer did not ensure that where there was a change in job assignments, authorized employees were retrained on safe application, methods, and means to isolate and control energy sources of that equipment.  Employees were not retrained in lockout/tagout prior to the change in job assignment of cleaning and/or unjamming the 02-Cryo cyclone equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $10210

1910.147 D

Repeat Gravity 10 1 instance 12 exposed
Issued
Aug 16, 2019
Abate by
Oct 15, 2019
Penalty
Initial $20,420 · Current $10,210 Reduced
29 CFR 1910.147(d): The established procedure for the application of energy control (the lockout or tagout procedures) did not cover the actions listed in and was not done in sequence as required by 29 CFR 1910.147(d)(1)-(6):  a. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 1, 2019, employees were exposed to amputation injury in that the 02-Cryo Line cyclone vent relief airlock was not locked out prior to unjamming activities.  The employer did not ensure energy control applications steps to control the electrical energy source were implemented prior to employees accessing the hazard area to remove rubber material from the cyclone's airlock; the employer did not:  - Turn off or shut down the equipment. - Physically operate energy isolating devices to control energy sources and affix lockout device(s). - Ensure that all potentially hazardous stored or residual energy was relieved, disconnected, and rendered safe. - Verify that isolation and deenergization of the machine or equipment had been accomplished.  Midwest Elastomers, Inc. was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.147(d) which was contained in OSHA inspection number 1223125, citation number 1, item number 1,  and was affirmed as a final order on July 6, 2017, with respect to a workplace located at 700 Industrial Dr., Wapakoneta, Ohio.
Recent events (2)
  • — I (R) $10210
  • — Z (R) $20420

1910.147 C04 II D

Other-than-serious 1 instance 12 exposed
Issued
Aug 16, 2019
Abate by
Sep 4, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy controls:  a. Midwest Elastomers, Inc. - Wapakoneta, Ohio: On or about May 1, 2019, the employer did not ensure that energy control procedures for the 02-Cryo line identified specific steps to verify energy control measures.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0