Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GOLDEN ACORN CASINO & TRAVEL CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GOLDEN ACORN CASINO & TRAVEL CENTER in 1800 GOLDEN ACORN WAY, CAMPO, CA 91906 (NAICS 713210). OSHA activity number 345437503.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Golden Acorn Casino & Travel Center — free Get an email when a new federal OSHA severe-injury report for Golden Acorn Casino & Travel Center is published. One employer, no account, unsubscribe in one click.
Site address
1800 GOLDEN ACORN WAY
City
CAMPO
State
CA
ZIP
91906
Mailing
1800 GOLDEN ACORN WAY, CAMPO, CA 91906
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713210
Employees
145
Ownership type
A

5 citations on file for this inspection.

1910.178 A06

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 9, 2021
Abate by
Jan 26, 2022
Penalty
Initial $7,022 · Current $4,915 Reduced
29 CFR  1910.178(a)(6): The employer did not ensure that all nameplates and markings were in place:  Facilities Maintenance Yard: Employees operated the Hyster Forklift(s) to move digital signs .  The Green Hyster A2 Forklift did not have the  instruction data nameplates  to indicate load limits of the forklift. This condition exposed the employees to forklift overloads which could cause forklifts to overturn and/or tip over hazard(s).
Recent events (2)
  • — I (S) $4915.4
  • — Z (S) $7022

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 9, 2021
Penalty
Initial $7,022 · Current $4,915 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Facilities Maintenance Shop:  Employee(s) used the electrical outlet to power powder coating and sandblasting equipment.  The outlet was tied into and extension cord cable which was used as fixed wiring.  Employees were exposed to electrical and/or fire hazards.
Recent events (2)
  • — I (S) $4915.4
  • — Z (S) $7022

1910.305 G01 IV B

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 9, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(B): Flexible cords and cables may not be used where run through holes in walls, ceilings or floors:  Casino Bar Storage Room: Flexible power cord (extension cord) had been plugged in at the bar storage room through a ceiling tile to power a multi-plug power strip.  Employees were exposed to fire and/or electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 9, 2021
Penalty
Initial $10,533 · Current $7,373 Reduced
29 CFR  1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:  Main Kitchen Prep Line:  Employee(s) stored perishable consumables in the Red Coca-Cola refrigerator.  The power cord to the fridge was damaged and covered with black tape. Employee(s) were exposed to fire and/or electrical hazards.
Recent events (2)
  • — I (S) $7373.1
  • — Z (S) $10533

1910.303 B02

Repeat Gravity 1 4 instances 11 exposed
Issued
Sep 9, 2021
Abate by
Oct 27, 2021
Penalty
Initial $10,532 · Current $7,372 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  In the follow locations, appliances were plugged into power taps and/or extension cords and were not used according to listing and labeling instructions.   a) Facilities Maintenance Trailer Shelf- Black Mini-refrigerator plugged into an orange extension cord. b) Main Kitchen Prep Line- The food warmer and Coke Machine. c) Bar - Fridge was daisy chained with a power tap and extension cord. d) Travel Center- Vendor Fridge(s) daisy chained with a power tap and extension cord    Employees were exposed to potential risk of fire and/or electrical shock.  The Golden Acorn Casino and Travel Center was previously cited for a violation of this occupational safety and health standard or its equivalent standard which was contained in OSHA inspection number 1369787, citation number 1, item number 4 and was affirmed as a final order on January 31, 2019 with respect to a workplace located at 1800 Golden Acorn Way CAMPO, CA. 91906
Recent events (2)
  • — I (R) $7372.4
  • — Z (R) $10532

View Golden Acorn Casino & Travel Center's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345437503.