Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MOAPA PAIUTE TRAVEL PLAZA

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MOAPA PAIUTE TRAVEL PLAZA in INTERSTATE 15 EXIT 75, MOAPA, NV 89025 (NAICS 713210). OSHA activity number 345590624.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Moapa Paiute Travel Plaza — free Get an email when a new federal OSHA severe-injury report for Moapa Paiute Travel Plaza is published. One employer, no account, unsubscribe in one click.
Site address
INTERSTATE 15 EXIT 75
City
MOAPA
State
NV
ZIP
89025
Mailing
P.O. BOX 340, MOAPA, NV 89025
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713210
Employees
35
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 3, 2021
Abate by
Dec 27, 2021
Penalty
Initial $8,778 · Current $1,463 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) On or about October 20, 2021 and at times prior to that date, for the employees exposed to electrical and/or fire hazards while preforming work activities in the IT room where two extension cords and three relocatable power taps (power strips) were series-connected located at Interstate 15 Exit 75, Moapa, Nevada.
Recent events (2)
  • — I (S) $1463
  • — Z (S) $8778

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 3, 2021
Abate by
Dec 27, 2021
Penalty
Initial $0 · Current $1,463
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  (a) On or about October 20, 2021 and at times prior to that date, for the employees exposed to electrical and/or fire hazards while preforming work activities in and around the electrical room where cardboard boxes filled with paper files were stored within 19 inches of the electrical panels located at Interstate 15 Exit 75, Moapa, Nevada.
Recent events (2)
  • — I (S) $1463
  • — Z (S) $0

1910.305 J02 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 3, 2021
Abate by
Dec 27, 2021
Penalty
Initial $0 · Current $1,463
29 CFR  1910.305(j)(2)(iv):A receptacle installed in a wet or damp location was not suitable for the location:  (a) On or about October 20, 2021 and at times prior to that date, for the employees exposed to electrical hazards while preforming work activities in the custodial room where a standard electrical receptacle was installed adjacent to a sink located at Interstate 15 Exit 75, Moapa, Nevada.
Recent events (2)
  • — I (S) $1463
  • — Z (S) $0

View Moapa Paiute Travel Plaza's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345590624.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.