YREKA, CA —
OSHA Inspection: U.S.D.A - FOREST SERVICE - KLAMATH NATIONAL FOREST
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S.D.A - FOREST SERVICE - KLAMATH NATIONAL FOREST in 1030 SOUTH MAIN ST, YREKA, CA 96097 (NAICS 924120). OSHA activity number 346756901.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S.D.A - FOREST SERVICE - KLAMATH NATIONAL FOREST
- Site address
- 1030 SOUTH MAIN ST
- City
- YREKA
- State
- CA
- ZIP
- 96097
- Mailing
- 1711 SOUTH MAIN STREET, YREKA, CA 96097
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 20
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.157 E03
- Issued
- Nov 3, 2023
- Abate by
- Dec 22, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Located at the Yreka Service Center, multiple portable fire extinguishers were not subjected to an annual maintenance check: 1. Three portable fire extinguishers were located in or near the road crew office with annual maintenance last completed in 2021. 2. One portable fire extinguisher was located in the genetics building storage area with an annual maintenance last completed in May 2022. 3. One portable fire extinguisher in the fire cache was last maintained in May 2022. Employees are exposed to fire hazards.
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Nov 3, 2023
- Abate by
- Dec 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. At the Yreka Service Center, five fire extinguishers were not mounted, located, and identified so that they were readily accessible to employees. Employees are exposed to fire hazards. 1). One fire extinguisher was on the floor in the fleet maintenance shop next to an out-of-service Rockwell drill press 2). Two fire extinguishers were on a table in the road crew office 3). One fire extinguisher was on the floor in the genetics building storage area 4). One fire extinguisher was near the road crew office on the floor The USDA - Forest Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.157(c)(1), which was contained in OSHA inspection number 1415093, citation number 1, item number 3 and was affirmed as a final order on 09/09/2019, with respect to a workplace located at 6409 N Air Terminal Rd, Douglas AZ 85607.
Recent events (1)
- — Z (R) $0
1910.253 B04 III
- Issued
- Nov 3, 2023
- Abate by
- Dec 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii):Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: At the Yreka Service Center in the fleet maintenance shop and the road crew maintenance shop, there were multiple oxygen cylinders stored less than 20 feet from acetylene fuel-gas cylinders or combustible materials, exposing employees to fire hazards. This was observed in the following areas: 1). In the fleet maintenance shop, one oxygen cylinder next to one acetylene cylinder with regulators attached on a welding cart lacking noncombustible barrier 2). In the fleet maintenance shop, two oxygen cylinders next to one acetylene cylinder, capped 3). In the road crew shop, one oxygen cylinder next to one acetylene cylinder, capped, near the wall and a set of jacks 4). In the road crew shop, one oxygen cylinder next to one acetylene cylinder on a welding cart lacking a noncombustible barrier The USDA - US Forest Service - Klamath National Forest was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.253(b)(4)(iii), which was contained in OSHA inspection number inspection 1481084, citation number 1, item number 2, and was affirmed as a final order on October 21, 2020, with respect to a workplace located at 538 Oak Knoll Road, Klamath River, CA 96050.
Recent events (1)
- — Z (R) $0
1910.305 B02 I
- Issued
- Nov 3, 2023
- Abate by
- Dec 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Located in the fleet maintenance shop, one outlet did not have a faceplate on it, exposing employees to electrical hazards. The USDA - Forest Service was previously cited for violations of this Occupational Safety and Health Standard 29 CFR 1910.305(b)(2)(i) which are contained in the following OSHA inspection numbers: 1). Inspection 1608178, citation number 1, item number 1, and was affirmed as a final order on 09/01/2022, with respect to a workplace located at 1090 Glendora Mountain Road, Glendora, CA 91741. 2). Inspection 1628769, citation number 2, item number 1, and was affirmed as a final order on 12/21/2022, with respect to a workplace located at 49870 State Hwy 139, Tulelake, CA 96134.
Recent events (1)
- — Z (R) $0
1910.303 G01
- Issued
- Nov 3, 2023
- Abate by
- Dec 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. Sufficient access and working space was not provided and maintained about electric equipment as required. 1.) Located in the fleet maintenance shop behind the door, there was insufficient space in front of the electrical panel powering lights and outlets. Items were in front of the panel including a first aid kit, a box, and cones and signs. 2). Located in the road crew maintenance shop, one electrical panel powering lights and outlets had a metal desk protruding into the minimum required working space in front of the panel. Employees are exposed to electrical and fire hazards. The U.S.D.A. - Klamath National Forest was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 1478849, citation number 2, item number 2 and was affirmed as a final order on 10/21/2020 with respect to a workplace located at 1711 South Main St, Yreka, CA 96097.
Recent events (1)
- — Z (R) $0
More inspections at U.S.D.A - Forest Service - Klamath National Forest
View U.S.D.A - Forest Service - Klamath National Forest's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346756901.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.