BRYAN, TX —
OSHA Inspection: BWAY CORPORATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BWAY CORPORATION in 1591 N. HARVEY MITCHELL PKWY, BRYAN, TX 77803 (NAICS 326199). OSHA activity number 340373323.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BWAY CORPORATION
- Site address
- 1591 N. HARVEY MITCHELL PKWY
- City
- BRYAN
- State
- TX
- ZIP
- 77803
- Mailing
- 1591 HARVEY MITCHELL PARKWAY, BRYAN, TX 77803
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 94
- Ownership type
- A
Citations
21 citations on file for this inspection.
1910.22 A02
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $4,000 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition: On or about February 9, 2015 and in times prior thereto, the drain from an overhead TRANE air conditioning unit was leaking water onto the floor below, exposing employees to the hazards of slips and falls. A 480 volt transformer and 120 volt extension cords were located on the floor below the AC, creating a hazard of electrical shock.
Recent events (2)
- — I (O) $2000
- — Z (S) $4000
1910.106 E02 II
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.106(e)(2)(ii): Flammable liquids were not stored in closed containers. On or about February 9, 2015 and in times prior thereto, a 55 gallon barrel of alcohol with a hole in it was tipped on its side to prevent it from leaking. The hole in the barrel created a fire hazard located in the outside utility area.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.132 A
- Issued
- Jul 30, 2015
- Penalty
- Initial $4,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: On or about February 9, 2015 and in times prior thereto, a forklift operator was driving without wearing his seat belt exposing to employee to the hazard of being ejected from the forklift. The forklift was being operated in the outside utility area and the road around this area.
Recent events (2)
- — I (S) $0
- — Z (S) $4000
1910.178 P01
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $2,000
General-duty citation text
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been taken out of service until restored to safe operating condition: On or about February 9, 2015 and in times prior thereto, located in the outside utility area, the employer did not ensure that the forklift's defects were promptly corrected, exposing employees to the hazards of being struck by and/or ejected from forklifts: a: The operator's seat and seat belt as part of the seat belt and hip restraint system were badly worn.
Recent events (2)
- — I (S) $2000
- — Z (S) $0
1910.215 A04
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: On or about February 9, 2015 and in times prior thereto, in the maintenance area, a DeWALT, DW 785, bench grinder had a work rest that was adjusted to 1 inch exposing employees to the hazards of being struck by piece being machined and/or pieces of stone.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.215 B09
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: On or about February 9, 2015 and in times prior thereto, on a DeWalt 758 bench grinder, the distance between the abrasive wheel periphery and the adjustable tongue guard was 1.25 inches.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.253 B04 I
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire: On or about February 9, 2015 and in times prior thereto, oxygen and acetylene cylinders were stored together, located in the outside utility area, exposing employees to the hazards of fire.
Recent events (2)
- — I (S) $3000
- — Z (S) $3000
1910.254 B04 IV
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $3,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.254(b)(4)(iv): Terminals for welding leads were not protected from accidental contact by personnel or metal objects: On or about February 9, 2015 and in times prior thereto, the power terminal boots were not put in place on a Miller Wildcat 200 welder to protect terminals. This condition created an arc flash hazard located in the maintenance area.
Recent events (2)
- — I (O) $1500
- — Z (S) $3000
1910.254 D07
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.254(d)(7): Electrode holders when not in use were not so placed that they could not make electrical contact with persons, conducting objects, fuel or compressed gas tanks: On or about February 9, 2015 and in times prior thereto, the electrode was left in the stinger on a Miller Wildcat 200 welder. This condition created an electrical hazard located in the maintenance shop.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 B01 II
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: On or about February 9, 2015 and in times prior thereto, the following electrical hazards were found in the production area; a. Baldor Relianget 460 volt motor had a conduit attached to the contactor box that was broken. b. 480 VAC disconnect marked "E1" for "I 14" Chiller had the load side conductor attached to a variable sized knock out. A ring of the knock out broke out leaving the attachment device ineffective. c. Metal armor conduit to grinding machine located in the grinding area was broken. d. 120 volt duplex and fourplex outlets, located in shipping and receiving on a metal pole near disconnect #3 had become detached from the support pole and were hanging from the supply cords. e. 480 volt metal conduit to starter near 30 KVA transformer, located in the grinding area was broken. f. 480 volt plastic conduit to Compressor #3 Kaeser, located in the outside utility area was broken.
Recent events (2)
- — I (S) $5000
- — Z (S) $5000
1910.303 F02
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about February 9, 2015 and in times prior thereto, the disconnects on the overhead buss were not identified as their purpose. The created an electrical hazard located throughout the production area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $4,000 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about February 9, 2015 and in times prior thereto, safe clearance was not provided in front of electrical equipment. This condition created an electrical hazard located in the following areas: a. In front of a 480 volt, 30 KVA transformer, located in the grinding room. b. 240 volt panel, located in maintenance department.
Recent events (2)
- — I (O) $2000
- — Z (S) $4000
1910.304 A02
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $4,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity: On or about February 9, 2015 and in times prior thereto, the following outlets were found to have reverse polarity creating an electrical hazard: a. Power cord to NALCO water treatment unit, located in the outside water treatment area. b. 4-outlet mounted to the wall below a 120 VAC fuse box above a shop table, located in the maintenance area.
Recent events (2)
- — I (S) $0
- — Z (S) $4000
1910.304 G05
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $2,000
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about February 9, 2015 and in times prior thereto, employees were exposed to the following ungrounded equipment, exposing employees to the hazards of electrical shock: a. 120 VAC - 4 plug outlet box mounted below electrical panel I2, located in the pail bay. b. 120 VAC extension cord to fan had a missing ground prong, located in the pail bay. c. 120 VAC candy machine was not ground, located in the break room.
Recent events (2)
- — I (S) $2000
- — Z (S) $0
1910.305 B01 I
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $4,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: On about February 9, 2015 and in times prior thereto, a 460 VAC conductor cable entering a hole in the cabinet of a Kompressor, DAL 1310150845-001 did not have a bushing guard. This electrical hazard was located in the outside utility area.
Recent events (2)
- — I (S) $0
- — Z (S) $4000
1910.305 G01 IV B
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors. On or about February 9, 2015 and in times prior thereto, a 120 volt extension cord was run through a hole in the wall. This electrical hazard was located in the maintenance area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 II
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $4,000 · Current $4,000
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: On or about February 9, 2015 and in times prior thereto, a yellow extension cord was spliced. This created an electrical hazard in the Nalco water treatment area.
Recent events (2)
- — I (O) $4000
- — Z (S) $4000
1910.305 G02 III
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about February 9, 2015 and in times prior thereto, the following equipment was not provided with proper strain relief, exposing employees to the hazards of electrical shock: a. A 480 VAC cord coming from the load side of disconnect 4, located in the shipping and receiving area. b. A 460 VAC cord entering the cabinet of Compare L75 RS air compressor, located in the outside utility area. c. A 480 VAC cord to unit 167 disconnect, located in the production area. d. A 480 VAC cord on the load side of Chiller I 14 disconnect, located in the pail area.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.333 B02
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): On or about February 9, 2015 and in times prior thereto, the 480 VAC cooling water pump motors were being repaired while energized and were not locked out. This created an electrical hazard, located in the cooling tower area.
Recent events (2)
- — I (S) $0
- — Z (S) $5000
1910.305 B01 II
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $20,000 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. On or about February 9, 2015 and in times prior thereto, the following equipment had open holes, exposing employees to the hazards of electrical shock: a. Four 1 inch holes were on top of a 120 VAC breaker box, located in front of clothes changing area. b. Two 1 inch holes under a 120 VAC breaker panel I2 with a fourplex attached, located in the pail bay. c. Two breaker slots were open on a large 480 VAC panel, located in the switch gear room. The B-Way Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(1)(ii), which was contained in OSHA inspection number 959843, citation number 1, item number 2 and was affirmed as a final order on August 13, 2014 with respect to a workplace located at 1591 N. Harvey Mitchell Parkway, Bryan, TX 77803.
Recent events (2)
- — I (S) $7000
- — Z (R) $20000
1910.305 B02 I
- Issued
- Jul 30, 2015
- Abate by
- Jul 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose; and each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about February 9, 2015 and in times prior thereto, the following equipment did not have covers, exposing employees to the hazards of electrical shock: a. A 120 volt duplex mounted to a post near the water treatment area, located in the shipping and receiving area. b. A 120 volt duplex mounted in the wall where a refrigerator was removed, located in the break room. c. A 120 volt low water level relay under I14 Chiller, located in pail bay. The B-Way Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(2)(I), which was contained in OSHA inspection number 959843, citation number 1, item number 3 and was affirmed as a final order on August 13, 2014 with respect to a workplace located at 1591 N. Harvey Mitchell Parkway, Bryan, TX 77803.
Recent events (2)
- — I (R) $0
- — Z (R) $0
More inspections at Bway Corporation
View Bway Corporation's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340373323.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.