OSHA Inspection: U.S. DEPT. OF INTERIOR - NATIONAL PARK SERVICE - SEQUOIA & KINGS CANYON

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPT. OF INTERIOR - NATIONAL PARK SERVICE - SEQUOIA & KINGS CANYON in RED FIR FACILITY 64600 GENERALS HIGHWAY, SEQUOIA NATIONAL PARK, CA 93262 (NAICS 712190). OSHA activity number 341651990.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Dept. of Interior - National Park Service - Sequoia & Kings Canyon for free Get an email when a new federal OSHA severe-injury report for U.S. Dept. of Interior - National Park Service - Sequoia & Kings Canyon is published. One employer, no account, unsubscribe in one click.
Site address
RED FIR FACILITY 64600 GENERALS HIGHWAY
City
SEQUOIA NATIONAL PARK
State
CA
ZIP
93262
Mailing
47050 GENERALS HIGHWAY, THREE RIVERS, CA 93271
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
570
Ownership type
Federal government (D)

6 citations on file for this inspection.

1910.304 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(a)(2): 29 CFR 1910.304(a)(2):  Grounded conductors were attached to terminals or leads so as to reverse designated polarity.    Plumbing Shop, Red Fir Facility, Sequoia National Park, 7/13/2016: Employees were exposed to electrical shock hazards when they worked with the RIDGID pipe threading machine which was energized by a double duplex receptacle that had reverse polarity.  The RIDGID pipe threading machine power cord was also missing the ground pin and the receptacle was not GFCI protected, which increased the probability of exposure.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    Plumbing Shop, Red Fir, Sequoia National Park, 7/13/2016:  Employees were exposed to electrical shock hazards when they worked with the RIDGID pipe threading machine which was missing its ground pin. The pipe threading machine was energized by a double duplex receptacle that had reverse polarity and was not GFCI protected, which increased the probability of exposure.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    Plumbing Shop, Red Fir Facility, Sequoia National Park, 7/12/2016: The 4 inch square duplex receptacle box, which was used to energize a tile cutter and a RIDGID pipe threading machine, had a 1 inch diameter unused opening that was not closed. Employees were exposed to electrical shock hazards if they were to come in contact with the live parts.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.253 B04 III

Repeat Gravity 1 1 instance 1 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:     Red Fir Roadway Division Maintenance Facility, Sequoia National Park, 7/13/2016: Oxygen and acetylene cylinders were stored together which exposed employees to fire and combustion hazards.    The U.S. National Park Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.253(b)(4)(iii), which was contained in OSHA inspection number 913208, citation number 02, item number 04 and was affirmed as a final order on 11/12/2013, with respect to a workplace located at 47050 Generals Highway, Three Rivers, CA 93271 (Ash Mountain Facility).
Recent events (2)
  • · I (R) $0
  • · Z (R) $0

1910.157 C01

Other-than-serious 1 instance 1 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.    Red Fir Maintenance Facility, Sequoia National Park, 07/13/2016: Two fire extinguishers were not mounted on the hanging brackets provided. The fire extinguishers were placed on the floor throughout the facility which exposed employees to tripping and fire hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.242 B

Other-than-serious 1 instance 1 exposed
Issued
Sep 16, 2016
Abate by
Nov 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i:    Red Fir Roadway Division Maintenance Facility, Sequoia National Park, 07/13/2016: The compressed air used for cleaning was not reduced to 30 p.s.i.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0